JUAL WAGO 750-495/040-001, 3-Phase Power Measurement; 690 VAC, 5 A; Extreme


Item no. 750-495/040-001
Description 3-Phase Power Measurement; 690 VAC, 5 A; Extreme
GTIN / EAN  4055143353588
Increase in order quantity (1, 2, 3, 4, ...) 
Customs Tariff no.   85365080990
Customs duty for the country of origin   DE
Manufacturer WAGO
Type of signal  Power measurement 
Resolution [bit] [Bit]  24 Bit
Bit width  2 x 128-bit data; 2 x 64-bit control/status 
Input resistance voltage path (typ.) [kΩ]  1429 kΩ 
Eingangswiderstand Strompfad typ.  5 mΩ 
Reference for measurement/output error  AC Strom/Spannung 
Measurement/output error, reference temperature [°C]  25 °C 
Measurement/output error, deviation from the largest measure  ±0.5 %
Measuring current (max.)  5 A 
Measuring cycle time  Adjustable for arithmetic mean value, Min_Max_Values 
Frequency range, power supply frequency  45 … 65 Hz 
Frequency range, harmonics analysis  0 … 3300 Hz 
Operating frequency [kHz]  15.9 kHz
Rated voltage  VLN = 400 VAC; VLL = 690 VAC 
Measurement components  Evaluating 
Measuring procedure  True RMS measurement 
System supply voltage  DC 5 V; via data contacts 
Current consumption, system supply [mA]  100 mA
Dielectric strength  AC 2,5 kV/DC 3,5 kV; gemäß EN 60870-2-1 
Connection technology: inputs/outputs  16 x CAGE CLAMP® 
Connection type (1)  Inputs/Outputs 
Solid conductor  0.25 … 2.5 mm² / 24 … 14 AWG 
Fine-stranded conductor  0.25 … 2.5 mm² / 24 … 14 AWG 
Strip length  8 … 9 mm / 0.31 … 0.35 Inch 
Width  24 mm / 0.945 in 
Height  67.8 mm / 2.669 in 
Height from upper-edge of DIN-35 rail  60.6 mm / 2.386 in 
Depth  100 mm / 3.937 in 
Type of mounting  DIN-35 rail 
Housing material  Polycarbonate, polyamide 6.6 
Weight [g]  91 g
Conformity marking  CE 
Surrounding air (operating) temperature  -40 … 70 °C 
Surrounding air (storage) temperature  -40 … 85 °C 
Degree of protection  IP20 
Degree of pollution (5)  2 (EN 60664-1) 
Mounting position  horizontal (standing/lying) or vertical 
Relative air humidity (no condensation) [%]  95 %
Exposure to pollutants  Per IEC 60068-2-42 and IEC 60068-2-43 
Permissible H2S contaminant concentration at a re  10 ppm 
Permissible SO2 contaminant concentration at a re  25 ppm 
Packaging type  Box 
Product Family  750 XTR Series I/O-System 
Main product function  Analog input 
Product type  Analog modules 
[mm]  24 mm