Item no. 750-482/000-001
Description 2-channel analog input; 4 … 20 mA HART; NAMUR NE 43
GTIN / EAN  4055143686327
Increase in order quantity (1, 2, 3, 4, ...) 
Customs Tariff no.   85389099990
Customs duty for the country of origin   DE
Manufacturer WAGO
Number of analog inputs  2 
Total number of channels (module)  2 
Type of signal  Current 
Type of signal current  DC 3.6 … 21 mA 
Sensor connection  2 x (2-conductor) 
Input filter  parametrizable 
Input filter: parametrizable (channel by channel)  yes 
Input voltage (max.)  24V 
Signal characteristic  Single-ended 
Resolution [bit] [Bit]  12 Bit
Overvoltage protection  30 V, reverse polarity protected 
Conversion time (typ.) [ms]  315 ms
Measurement/output error, reference temperature [°C]  25 °C 
Measurement/output error, deviation from the largest measure  ±0.2 %
Temperature coefficient of largest measurement range [%/K]  ±0.01 %/K
Line break detection  I meas < 1.0 mA 
Short circuit detection  I meas > 23 mA 
System supply voltage  DC 5 V; via data contacts 
Current consumption, system supply [mA]  25 mA
HART devices per channel  1 device (single-drop, no multi-drop) 
HART modems per channel  1 modem (no multiplex) 
Isolation  300 VAC system/supply 
Number of incoming power jumper contacts  2 
Number of outgoing power jumper contacts  2 
Connection technology: inputs/outputs  16 x CAGE CLAMP® 
Connection type (1)  Inputs/Outputs 
Solid conductor  0.08 … 2.5 mm² / 28 … 14 AWG 
Fine-stranded conductor  0.08 … 2.5 mm² / 28 … 14 AWG 
Strip length  8 … 9 mm / 0.31 … 0.35 Inch 
Width  24 mm / 0.945 in 
Height  67.8 mm / 2.669 in 
Height from upper-edge of DIN-35 rail  60.6 mm / 2.386 in 
Depth  100 mm / 3.937 in 
Type of mounting  DIN-35 rail 
Housing material  Polycarbonate, polyamide 6.6 
Weight [g]  94.16 g
Conformity marking  CE 
Surrounding air (operating) temperature  0 … 55 °C 
Surrounding air (storage) temperature  -40 … 85 °C 
Degree of protection  IP20 
Degree of pollution (5)  2 per IEC 61131-2 
Operating altitude  0 … 2000 m 
Mounting position  horizontal (standing/lying) or vertical 
Relative air humidity (no condensation) [%]  95 %
Vibration resistance  acc. to IEC 60068-2-6 
Shock resistance  15g per IEC 60068-2-27 
EMC immunity to interference  acc. to EN 61000-6-2 
EMC emission of interference  acc. to EN 61000-6-3 
Exposure to pollutants  Per IEC 60068-2-42 and IEC 60068-2-43 
Permissible H2S contaminant concentration at a re  10 ppm 
Permissible SO2 contaminant concentration at a re  25 ppm 
Product Family  750/753 Series I/O-System 
Main product function  Analog input 
Product type  Analog modules 
[mm]  24 mm