JUAL WAGO 750-460/000-005, 4-channel analog input; For Ni1000/RTD resistance sensors


Item no. 750-460/000-005
Description 4-channel analog input; For Ni1000/RTD resistance sensors
GTIN / EAN  4045454848965
Increase in order quantity (1, 2, 3, 4, ...) 
Customs Tariff no.   85389099990
Customs duty for the country of origin   DE
Manufacturer WAGO
Number of analog inputs  4 
Total number of channels (module)  4 
Type of signal  Resistance measurement 
Sensor connection  4 x (2-conductor) 
Bit width  4 x 16-bit data; 4 x 8-bit control/status (optional) 
Resolution (over entire range)  0.1 °C 
Conversion time (typ.) [ms]  250 ms
Measurement/output error, reference temperature [°C]  25 °C 
Measurement/output error, deviation from the largest measure  ±0.2 %
Temperature coefficient of largest measurement range [%/K]  ±0.01 %/K
Measuring current (typ.)  0.5 mA 
Sensor types  Ni 1000 TK6180 
Temperature range  -60 … +250 °C 
System supply voltage  DC 5 V; via data contacts 
Current consumption, system supply [mA]  65 mA
Isolation  500 V system/supply 
Connection technology: inputs/outputs  8 x CAGE CLAMP® 
Connection type (1)  Inputs/Outputs 
Solid conductor  0.08 … 2.5 mm² / 28 … 14 AWG 
Fine-stranded conductor  0.08 … 2.5 mm² / 28 … 14 AWG 
Strip length  8 … 9 mm / 0.31 … 0.35 Inch 
Width  12 mm / 0.472 in 
Height  69.8 mm / 2.748 in 
Height from upper-edge of DIN-35 rail  62.6 mm / 2.465 in 
Depth  100 mm / 3.937 in 
Type of mounting  DIN-35 rail 
Color  light gray 
Housing material  Polycarbonate, polyamide 6.6 
Weight [g]  51.8 g
Conformity marking  CE 
Surrounding air (operating) temperature  0 … 55 °C 
Surrounding air (storage) temperature  -40 … 85 °C 
Degree of protection  IP20 
Degree of pollution (5)  2 per IEC 61131-2 
Operating altitude  0 … 2000 m 
Mounting position  horizontal (standing/lying) or vertical 
Relative air humidity (no condensation) [%]  95 %
Vibration resistance  acc. to IEC 60068-2-6 
Shock resistance  15g per IEC 60068-2-27 
EMC immunity to interference  acc. to EN 61000-6-2 
EMC emission of interference  acc. to EN 61000-6-4 
Exposure to pollutants  Per IEC 60068-2-42 and IEC 60068-2-43 
Permissible H2S contaminant concentration at a re  10 ppm 
Permissible SO2 contaminant concentration at a re  25 ppm 
Packaging type  BOX 
Product Family  750/753 Series I/O-System 
Main product function  Analog input 
Product type  Analog modules 
[mm]  12 mm